D-HURRIKAN OF
Generel Data / model | 7/975 | 8,5/975 | 10/930 |
---|---|---|---|
Thermal output 70/103 °C | 208 kW | 228 kW | 237 kW |
Thermal output 30/60 °C | 35 kW | 36 kW | 34 kW |
Recoverable thermal output ¹ | 243 kW | 264 kW | 271 kW |
Fuel cosumption (Hu=10,0 kW/Nm³) | 26,9 Nm³/h | 29,2 Nm³/h | 29,9 Nm³/h |
Power requirement (kW) | 4,0 kW | ||
BUS-System | Modbus TCP | ||
Remote maintenance TCP/IP | yes | ||
Engine | |||
Type | R6 | ||
Engine displacement | 8,4 Liter | ||
Engine Type | Naturally aspirated | ||
Brennstoffeinsatz ² | 328 kW | ||
RPM | 1800 min-1 | ||
ISO standard power (mech.) ² | 120 kW | ||
Engine cooling water heat quantity | 111 kW | ||
Exhaust gas heat capacity 110 °C | 75 kW | ||
Efficieny Thermal ² | 56,7% | ||
Efficieny Combined (el. + th.) ² | 93,3% | ||
Engine oil | semi-synthetic | ||
Lubrication oil consumption | 60 g/Bh | ||
Filling capacity lubricant (max.) | 45 + 150 Liter | ||
Compressor | |||
Manufacturer | Atlas Copco | ||
Heat recovery compressor | 79 kW | 86 kW | 89 kW |
outlet pressure, barg ³ | 7 | 8,5 | 10 |
Free air delivery (FAD), m³/min ³ | 16,3 | 16,3 | 15,6 |
Modulation / power control | 60% - 100% | ||
compressed air connection | DN 80 PN 16 | ||
Gas supply | |||
Gas train | Nach DIN | ||
Interface Gas | DN 40 (1 1/2") | ||
Gas flow pressure | 30 - 50 mbar | ||
Air supply | |||
Combustion air mass flow | 405 kg/h | ||
Air temperature | 25°C | ||
Exhaust | |||
Interface Exhaust | DN 150 | ||
TA-Luft | yes | ||
Exhaust temperature | 620°C | ||
Condensate mass flow | 108 kg/h | ||
Max. permissible back pressure | < 15 mbar | ||
flow rate, dry | 349 Nm³/h | ||
mass flow, wet | 428 kg/h | ||
Hydraulic integration | 30/60 | 70/103 ⁴ | |
Interface inlet/outlet | DN 50 (2") | DN 50 (2") | |
Norm in-/outlet temperatur | 30 / 60°C | 70 / 103 °C 4) | |
Standard flow rate | 2 m³/h | 6,1 m³/h | |
Heating water pressure | 2,5 bar | 4 bar | |
Dimensions / Weight | |||
Dimensions (LxWxH) | 3655x1400x2000 mm | ||
Weight Module (w/o operating fluids) | 3.900 kg | ||
Dimensions housing (LxWxH) | 3600x1630x2100 mm | ||
Weight housing | 650 kg | ||
Dimensions cabinet (LxWxH) | 1200x1200x400 mm | ||
Weight cabinet | 130 kg | ||
Recommended concrete strength | C20/25 | ||
Payload, qk | 3,5 kN/m² | ||
Noise emissions (incl. standard silencer) | |||
Unit 1 m / 10 m | 75 / 65 dB(A) | ||
Exhaust gas stack 10 m | 67 dB(A) | ||
Exh. emissions with catalytic converter | |||
NOX | ≤ 250 mg/Nm³ | ||
CO | ≤ 250 mg/Nm³ | ||
HCHO | ≤ 5 mg/Nm³ | ||
Protection class | |||
Unit | IP 23 | ||
Unit with housing | IP 53 | ||
Control cabinet | IP 55 | ||
Options | |||
Housing | yes | ||
Additional silencer | yes | ||
Emergency cooler | yes | ||
Gas warning system | yes | ||
Knock control | yes | ||
Gross calorific value | yes | ||
Additional lubrication oil tank | yes | ||
LTE / UMTS-modul | yes | ||
BUS-converter | yes | ||
Heat meter (calibrated) | yes | ||
Neutralisation plant | yes | ||
Compressed air flow meter | yes | ||
Containerised solution | yes | ||
Remote control | yes | ||
Directly heated adsorption dryers | yes | ||
Master Control readynes | yes | ||
Contribution, installation, commisioning | yes |
¹ with a tolerance of ±7%; ² acc. to ISO 3046-1; ³ acc. to ISO 1217, Anh. D.;
⁴ max. possible temperature up to 108 °C
⁴ max. possible temperature up to 108 °C
Your contact person
Michael Portwich
m.portwich@altairnative.de
+49 172 3496 551